Selec EM4M Three phase DIN RAIL Energy Meter
Selec EM4M Three phase DIN RAIL Energy Meter
Regular price
Rs. 4,257.00
Regular price
Rs. 8,513.00
Sale price
Rs. 4,257.00
Unit price
/
per
Manufacturer | Selec |
Select Model | EM4M |
Display Specifications | |
Display | 3 rows, LCD with backlight |
Digits | 1 row of 4 digits and 2 rows of 7 digits |
LED Indications | Pulse Indication |
Display Scrolling | Automatic / Manual (Programmable) |
Display Reset | Programmable (For energy) |
Input Specifications | |
Electrical Connection | 1Ø – 2W (P1, P2, P3), 3Ø – 3W, 3Ø – 4W |
Input Voltage Range | 85-285V AC (L – N), 150-494V AC (L – L) |
Input Current Range | Ib: 10 A (Min – 0.5A, Max – 100A) |
Frequency | 45 to 65 Hz |
Power Consumption | 1.6VA |
Resolution | For energy: 0.01k For Power, Voltage, Current: Auto resolution For Power Factor: 0.01 |
Accuracy | Voltage (L – N): ±0.5% of F.S. Current: ±0.5% of Nominal Power factor: ±0.01 of F.S. Frequency: ±0.2% of Nominal Power (Active, Reactive, Apparent): Class 1 Energy (Active: Class 1, Reactive: Class 2) |
Memory Retention | 10 years (For Energy) |
Measuring Parameters | Voltage, Current, Frequency, Power factor, Power (Active, Reactive & Apparent), Energy (Active, Reactive & Apparent) Active, Reactive (Import / Export) & Max demand power |
Output Specifications | |
2 Pulse Outputs | Voltage range: 5 to 24V DC@100mA Pulse duration: 0.05 to 2.0 Sec. settable Pulse width: 1 / 10 / 100 / 1000 for kVARh (First pulse output is fixed 1000 pulses per kWh) |
Communication Interface and Protocol | RS485 and MODBUS RTU |
Communication Address | 1 to 255 (Programmable) |
Transmission Mode | Half Duplex |
Transmission Distance | 500 meter maximum |
Transmission Speed | 2400 / 4800 / 9600 / 19200 / 38400 |
Parity | None, Odd, even |
Stop bits | 1 or 2 |
Response Time | 100ms (max and independent of baud rate) |
Supply Voltage | 176 to 276V AC (Self – Powered) |
Temperature | Operating Temperature: -10 to 55C Storage Temperature: -20 to 75C |
Humidity (non-condensing) | Upto 85% RH |